HSL (TR-Series)
Air-Cooled GensetTechnical Data Sheet
|
GENSETS |
Single-Phase |
three-Phase |
|
220 V |
380/220 V |
|
230 V |
400/230 V |
|
240 V |
415/240 |
|
MODEL |
Engine |
Rating |
kVA |
kW |
kVA |
kW |
HSL8
HSL8A |
TR1 |
Prime |
4.4 |
4.4 |
5.8 |
4.7 |
|
Standby |
4.8 |
4.8 |
6.5 |
5.2 |
HSL15
HSL15A |
TR2 |
Prime |
9.1 |
9.1 |
11.9 |
9.5 |
|
Standby |
10.0 |
10.0 |
13.1 |
10.5 |
|
HSL24
HSL24A |
TR3 |
Prime |
13.9 |
13.9 |
18.4 |
14.7 |
|
Standby |
15.3 |
15.3 |
20.3 |
16.2 |
|
60 Hz 1800 r
/ min |
|
GENSETS |
Single-Phase |
three-Phase |
|
220 V |
380/220 V |
|
230 V |
400/230 V |
|
240 V |
415/240 |
|
MODEL |
Engine |
Rating |
kVA |
kW |
kVA |
kW |
HSL8
HSL8A |
TR1 |
Prime |
5.5 |
5.5 |
7.2 |
5.8 |
|
Standby |
6.1 |
6.1 |
8.0 |
6.4 |
HSL15
HSL15A |
TR1 |
Prime |
11.1 |
11.1 |
14.4 |
11.6 |
|
Standby |
12.2 |
12.2 |
15.9 |
12.7 |
HSL24
HSL24A |
TR1 |
Prime |
17.1 |
17.1 |
22.6 |
18.1 |
|
Standby |
18.8 |
18.8 |
24.9 |
19.9 |
|
|
Approximate Fuel Consumption |
| |
Litres/Hour |
|
Gensets |
Load |
50 Hz 1500
r / min |
50 Hz 1500
r / min |
HSL8
HSL8A |
100% |
1.5 |
1.9 |
|
75% |
1.2 |
1.5 |
HSL15
HSL15A |
100% |
3.1 |
3.7 |
|
75% |
2.4 |
2.9 |
HSL24
HSL24A |
100% |
4.6 |
5.5 |
|
75% |
3.6 |
4.3 |
|
Acoustic set Sound Pressure Levels |
|
Gensets |
dBA,
at 75% Load |
50 Hz 1500
r / min |
50 Hz 1500
r / min |
|
HSL8A |
60 |
61 |
|
HSL15A |
60 |
61 |
|
HSL24A |
60 |
61 |
| |
Rating Definitions to
IS08S28-1
All
ratings in the table are in accordance with
ISO 8528-1. Power Factor: Single phase, 1.0
pf; three-phase, 0.8 pf.
Rating Conditions
A standard generating set is designed to
opetare in environmental reference
conditions of 25 °C, 100 kPa and 30%
humidity.
Prime power
This rating is for the supply of continuous
electrical power (at variable load). There
is no limit on the annual hours of operation
and 10% overload power can be supplied for 1
hours in 12
Standby power
This rating is for the supply of continuous
electrical power
(at variable load) in the event of a utility
power failure.
No overload is permitted
Optional items: |
-
Residential exhaust Silencer
for open sets (as fitted to acoustic
version) AMF upgrade Kit
-
Acoustic canopy kit (including
residential silencer kit) for
retro-fitting to manual/ remote start
open sets only
-
2-wheel trailer
-
Basic tool kit
Engine Specification
-
Lister Petter TR-Series, Air-cooled,
direct injection, naturally aspirated
diesel engine
-
Medium-duty air cleaner
-
Oil and fuel filters
-
Fuel-lift pump
-
12 V electric starting system
Alternator Specification
-
Leroy Somer/Stamford make
-
Single-bearing, 4-pole brushless
alternator
-
Solid state AVR with=1.5% voltage
-
Regulation as standard
-
Class "H" insulation on the rotor and
stator
-
IP23 protection class
|
 |
|
Acomprehensive range of
options allow you to Select
a Specification that matches
your requirements.
Please ask your distributor.
(See panel below |
|
|
|
|