HSL (TR-Series) Air-Cooled GensetTechnical Data Sheet
 

50  Hz  1500  r / min

GENSETS Single-Phase three-Phase
220 V 380/220 V
230 V 400/230 V
240 V 415/240

MODEL

Engine Rating kVA kW kVA kW
HSL8
HSL8A

TR1

Prime 4.4 4.4 5.8 4.7

Standby

4.8 4.8 6.5 5.2
HSL15
HSL15A
TR2 Prime 9.1 9.1 11.9 9.5
Standby 10.0 10.0 13.1 10.5

HSL24
HSL24A

TR3 Prime 13.9 13.9 18.4 14.7
Standby 15.3 15.3 20.3 16.2

60  Hz 1800 r / min

GENSETS

Single-Phase three-Phase
220 V 380/220 V
230 V 400/230 V
240 V 415/240
MODEL Engine Rating kVA kW kVA kW
HSL8
HSL8A
TR1 Prime 5.5 5.5 7.2 5.8
Standby 6.1 6.1 8.0 6.4
HSL15
HSL15A
TR1 Prime 11.1 11.1 14.4 11.6
Standby 12.2 12.2 15.9 12.7
HSL24
HSL24A
TR1 Prime 17.1 17.1 22.6 18.1
Standby 18.8 18.8 24.9 19.9

Approximate Fuel Consumption

 

Litres/Hour

Gensets Load 50 Hz 1500
r / min
50 Hz 1500
r / min
HSL8
HSL8A
100% 1.5 1.9
75% 1.2 1.5
HSL15
HSL15A
100% 3.1 3.7
75% 2.4 2.9
HSL24
HSL24A
100% 4.6 5.5
75% 3.6 4.3

Acoustic set Sound Pressure Levels

Gensets

dBA, at 75% Load

50 Hz 1500
r / min
50 Hz 1500
r / min
HSL8A 60 61
HSL15A 60 61
HSL24A 60 61
 

Rating Definitions to IS08S28-1

All ratings in the table are in accordance with ISO 8528-1. Power Factor: Single phase, 1.0 pf; three-phase, 0.8 pf.
Rating Conditions
A standard generating set is designed to opetare in environmental reference conditions of 25 °C, 100 kPa and 30% humidity.
Prime power
This rating is for the supply of continuous electrical power (at variable load). There is no limit on the annual hours of operation and 10% overload power can be supplied for 1 hours in 12
Standby power
This rating is for the supply of continuous electrical power
(at variable load) in the event of a utility power failure.
No overload is permitted


Optional items:

  •  Residential exhaust Silencer for open sets (as fitted to acoustic version)
    AMF upgrade Kit

  • Acoustic canopy kit (including residential silencer kit) for retro-fitting to manual/ remote start open sets only

  • 2-wheel trailer

  • Basic tool kit

    Engine Specification

  • Lister Petter TR-Series, Air-cooled, direct injection, naturally aspirated diesel engine

  • Medium-duty air cleaner

  • Oil and fuel filters

  • Fuel-lift pump

  • 12 V electric starting system

    Alternator Specification

  • Leroy Somer/Stamford make

  • Single-bearing, 4-pole brushless alternator

  • Solid state AVR with=1.5% voltage

  • Regulation as standard

  • Class "H" insulation on the rotor and stator

  • IP23 protection class

    Acomprehensive range of options allow you to Select a Specification that matches your requirements.