SAME DEUTZ-FAHR

TECHNIOCAL DATA

 
GENERATING SET GENSET MODEL S 20W S 20W S 35W S 40 S 50
  PRIME POWER
RATING (KVA/KW)
20/16 30/24 35/28 40/32 50/40
  CURRENT(Amps) 28 42 49 56 70
  SPECIFIC FUEL
CONSUMPTION
(gms/bhop-hr) @
100% Load Factor

151

147 164 150 144
ENGINE ENGINE MAKE SAME DEUTZ SAME DEUTZ SAME DEUTZ SAME DEUTZ SAME DEUTZ
 

MODEL

1000.2W 1000.3W 1000.3WT 1000.4W 1000.4WT
 

BHP

25

38

52

52

60

  COOLING WATER COOLED WATER COOLED WATER COOLED WATER COOLED WATER COOLED
 

ASPIRTION

NATURAL NATURAL TURBO CHARGED NATURAL TURBO CHARGED
  NO.OF CYLINDER 2 3 3 4 4
  RPM 1500 1500 1500 1500 1500
  BORE (mm) 105 105 105 105 105
  STROKE(mm) 115.5 115.5 115.5 115.5 115.5
 

COMPRESSION
RATIO

17.1 17.1 16.1 17.1 16.1
  DISPLACEMENT
(LTRS.)
2.0` 3.0 3.0 4.0 4.0
  FUEL HSD HSD HSD HSD HSD
  GOVERNOR MECH MECH MECH MECH MECH
  CLASS OF
GOVERNING
A A A A A
  STARTING SYS. 12V (ELEC.) 12V (ELEC.) 12V (ELEC.) 12V (ELEC.) 12V (ELEC.)
  LUB OIL SPEC. 20W40 20W40 20W40 20W40 20W40
  LUB OIL SUMP
CAPACITY (LTRS)
 
7.5 7.5 7.5 7.5 7.5
  LUBRICATING
OIL FILTER
SPIN ON
REPLACEABLE
TYPE
SPIN ON
REPLACEABLE
TYPE
SPIN ON
REPLACEABLE
TYPE
SPIN ON
REPLACEABLE
TYPE
SPIN ON
REPLACEABLE
TYPE
  EXHAUST SIZE 2.5" 3" 3" 3" 3"
ALTERNATOR VOLTAGE 415V 415V 415V 415V 415V
  RPM/FREQ 1500 /50 HZ. 1500 /50 HZ. 1500 /50 HZ. 1500 /50 HZ. 1500 /50 HZ.
  NO.PHASES 3 PHASE 3 PHASE 3 PHASE 3 PHASE 3 PHASE
  POWER FACTOR 0.8 (lag) 0.8 (lag) 0.8 (lag) 0.8 (lag) 0.8 (lag)
  ENCLOSURE IP 23 IP 23 IP 23 IP 23 IP 23
  VOLT.REG.
(MAX)
±1,5% ±1,5% ±1,5% ±1,5% ±1,5%
  CLASS OF
INSULATION
II CLASS H CLASS H CLASS H CLASS H CLASS
  RECOMMENDED
CABLE SIZE (ALL ARMOURED)
16 sq. mm
(3 Vi core)
16 sq. mm
(3 Vi core)
16 sq. mm
 (3 Vi core)
16 sq. mm
(3 Vi core)
16 sq. mm
(3 Vi core)
  ENCLOSURE IP 42 IP 42 IP 42 IP 42 IP 42
  BREAKING RATING (Amps) 50 50 63 63 80
  RATING (All) RATING (AH) 120 AH 12V 120 AH 12V 120 AH 12V 120 AH 12V